Full Length Research Paper
ABSTRACT
Legionnaires disease can be acquired through exposure to Legionella pneumophila, a gram-negative bacteria ubiquitous in both natural and engineered water systems. Over the years, a number of disinfection techniques notably, chlorination, ozonation, thermal, UV and copper-silver ionization have been employed across different kinds of engineered water systems with diverse measures of success. Available evidence portends, most of the aforementioned techniques often have to be combined to achieve long-term efficacy. Remarkably, albeit the extensive research and reportage on Legionnaires outbreak in the developed world, very few studies have been carried out with regards to Africa. We reviewed existing literature on the application of the aforementioned techniques in buildings. Our study concurs with earlier studies; most of the disinfection techniques will have to be combined to achieve the desired efficacy. We found very scanty studies on Legionella or reportage of its outbreak within Africa. Our study also found very little in terms of any of the techniques been applied with the specific aim of reducing Legionella proliferation in engineered water systems within Africa. This is alarming, especially, on a continent where several communities have little or no access to quality water and healthcare. In light of the above, stronger measures such as sensitization, properly managed water distribution systems, as well as policies aimed at enforcing national and international guidelines on Legionella control is recommended.
Key words: Legionnaires disease, water disinfection, engineered water system, Africa.
INTRODUCTION
Legionnaire’s disease first commanded attention in 1976 during an American Legion convention in Philadelphia (Swanson and Hammer, 2000). Whilst initial documentation on Legionnaires was related to cooling towers, a study by Tobin et al. (1981) was one of the earliest to demonstrate Legionella could be found in water distribution systems of hotels and hospitals. Their study demonstrated infected water systems could be linked with cases of Legionnaires in the absence of air-conditioning equipment. Legionnaires is largely caused by Legionella pneumophila a pathogenic bacteria for free living, ubiquitous, freshwater, and soil amoebae of the genera Acanthamoeba and Naegleria (Rowbotham, 1980). The disease is characterized by pneumonia, often afflicting the elderly or immunosuppressed individuals (Parry et al., 1985; Kümpers et al., 2008; Hilbi et al., 2010). Although Legionella is a genetically diverse species, L. pneumophila, one of the many Legionella species, is common in natural and engineered water systems and its single serogroup, L. pneumophila Sg1 accounts for almost 84% of Legionnaire's cases reported world wide (Cold Spring Harbor Laboratory, 2008). Though several disinfection modalities have been tested and approved over the years, the dilemma in choosing an efficacious technology still lingers. The application and draw backs of most of the contemporary techniques employed continue to be evaluated whilst new techniques or devices aimed at Legionella control in water systems are still being experimented. Perhaps, this is because each of the techniques presents distinct characteristics (Marchesi et al., 2011). Over the last two decades, most of the notably documented techniques (e.g. superheating, copper-silver ionization, ozonation, Ultra violet light and hyper chlorination) have undergone evaluation and review in literature elsewhere (Kim et al., 2002a; Campos et al., 2003; Lin et al., 2002; Muraca et al., 1987; Muraca et al., 1990; Lin et al., 1998, 2011). Despite the above, these reviews along with documented efficacies often do not include Africa. While Legionella sampling in water systems is almost a routine in developed nations. Legionnaires disease is barely a subject in most African countries. Most patients are sub optimally treated for other diseases such as Tuberculosis in the face of likely symptoms. Owing to the fact that Legionella is ubiquitous in both natural and manmade water systems (CDC, 2016), the aforesaid is particularly disturbing considering the fact that piped-in water is non-existent in the poorest 40% of households in rural sub Saharan Africa (UNDESA, 2014). In this study, we review literature on some of the most commonly used techniques in Legionella control in engineered water systems. Keen attention is paid to water quality as well as the application of the respective techniques on the continent.
METHODS
The documented efficacy, advantage, disadvantage and effect on water quality of a number of disinfection modalities aimed at Legionella control and elimination was carried out. Thermal disinfection, hyper-chlorination, copper-silver ionization, ozonation and UV light were selected, taking into consideration similar reviews of the afore listed along with other techniques (Kim et al., 2002a; Campos et al., 2003; Lin et al., 1998). With the exception of copper silver ionization, the techniques were also selected based on existing evidence of their application across Africa for regular water treatment. Copper silver ionization was however added based evidence of its “positive” reviews in other literature. Finally, the review also sought to put together, documented efficacy in hospitals, hotels and water distribution networks; uncharacteristic of majority of such reviews.
CLASSIFICATION OF WATER DISINFECTION TECHNOLOGIES IN LEGIONELLA CONTROL
Water disinfection employed in Legionella control is varyingly classified. In certain literature, the techniques are classified as “localised methods” or point of use e.g. ozonation, UV lights and “systemic” e.g. thermal disinfection or copper silver ionization (Peiró Callizo et al., 2005). Other literature also groups the techniques as systemic or emergency disinfection (Lin et al., 2011). Emergency techniques such as thermal disinfection often employed during outbreaks have been reported to lack residual effects over longer periods (Stout et al., 1986; Chen et al. 2005; Mouchtouri et al., 2007), while disinfection techniques such as copper-silver ionization which have been linked with long term Legionella control are still under evaluation albeit being implemented (Cachafeiro et al., 2007).
THERMAL DISINFECTION (“HEAT AND FLUSH”)
Method
Water temperature greater than 60°C inhibits the survival 19 and growth of L. pneumophila in vitro (Muraca et al., 1987, 1990; Campos et al., 2003). Although one of the earliest in Legionella control, available literature suggests it is inefficacious unless repeatedly applied alongside faucets chlorine disinfection (Stout et al., 1986; Mouchtouri et al., 2007). Nonetheless, the temperature range for proliferation (20á´¼C to 43á´¼C) as well as inactivation (>44á´¼C, < 20á´¼C) are well documented (Konishi et al., 2006; Schulze-Robbecke and Buchholtz, 1992). Though varying forms of implementing this technique exists, the basic principle involves elevating the temperature of water in a storage tank above 70á´¼C while ensuring temperatures at distal fixtures are not below 60á´¼C. Distal fixtures may then be run at respective time intervals for days and monitored in accordance with required standards or regulations.
Characterization of efficacy, advantages and disadvantages
In a review, Campos et al. (2003), described thermal disinfection as a temporal control strategy as bacteria colonization is often evident months after implementation. Perhaps, due to ‘repository biofilm’ which provide protective mechanism for survival and re-colonization, complete elimination of Legionella in water systems remains farfetched (Mouchtouri et al., 2007). The above is evident in a study by Steinert et al. (1998), who observed re-colonization of two Legionella strains, three months after implementing the technique (70°C) in a hospital water system (Figure 1). A study by Chen et al. (2005), also observed regrowth’s, two months after implementing the technique at a medical centre (Figure 1). Other studies have also reported insignificant reduction in Legionella contamination counts within the first months of its implementation (Marchesi et al., 2011). In terms of its edge over other disinfection techniques, thermal disinfection does not require any special equipment’s aside the use of devices that register water temperature. It can be implemented expeditiously in cases of outbreaks or emergencies. On the other hand, the possibility of scalding and the amount of work involved in monitoring distal sites could be time consuming. Challenges with its application in larger buildings e.g. hotels or hospitals where stable temperature may be difficult to attain along entire water networks is also noteworthy (Chen et al., 2005; Mouchtouri et al., 2007). In view of the afore-stated, routine implementation could be challenging especially as such facilities (Hotels or hospitals) will have to be unoccupied at best. Finally, dead legs, operation at deliberate low temperatures per concerns of scalding, as well as its implementation in old water distribution networks are also noteworthy inhibitions (Groothuis et al., 1985; Plouffe et al., 1983).
Effect of thermal disinfection on water quality and its application in Africa
The overall effect of thermal disinfection on water quality remains conspicuously better than other water disinfection technologies especially due to lack of biocidal effect of chemicals as may be the case in other disinfection modalities. Minus “circulation“ through the water distribution network along with “special devices“ that monitor water temperature at distal sites, the technique is almost synonymous to boiling which remains perhaps, one of the default household water treatment methods in the developing world (Rosa and Clasen, 2010). Evidence of easy contamination after cooling coupled with economic and environmental unsustainability in its application (Luby et al., 2000; Gilman and Skillicorn 1985; Parikka, 2004) perchance, remains the defining reason why the technique is not used as a routine water disinfection modality. Interestingly, boiling remains relatively rare in Africa (4.5%) even though other African countries such as Uganda (39.8%) and Zambia (15.2%) report significantly high rates of its application (Rosa and Clasen, 2010). Nonetheless, whereas boiling will serve the same purpose of Legionella inactivation (> 70°C), evidence of literature on boiling or heat treatment specifically aimed at Legionella control is almost nonexistent. Boiling is however largely documented as a household water treatment method.
HYPER CHLORINATION
Method
Hyper chlorination involves the addition of chlorine to water with existing chlorine residue. So far, two ways of implementing the technique has been documented: (1) Shock hyper chlorination, which involves the pulse injection of chlorine into a given water system (range of 20 to 50 mg/l), and (2) continuous chlorination which involves continuous injection of chlorine in a form of gas, liquid or solid. The treated water is later drained and fresh water introduced to reduce chlorine concentration to about 0.5 to 1 mg/l. Typically, the installation involves, mounting chlorine injectors in highly pressured water supply lines with venturi orifice which create a vacuum; consequently, drawing chlorine gas into the water stream. Overall, adequate contact time and mixing is required to achieve desired efficacy.
Characterization of efficacy, advantages and disadvantages
Although the technique represents the decisive treatment for bacteria control and elimination in most water systems most especially in old water distribution networks (Schoenen, 2002; Orsi et al., 2014), Legionella is reported to be more tolerant to chlorine than other bacteria including Escherichia coli (World Health Organization (WHO), 2007). Evidence of the presence of biofilm is reported to be a key element in its ability to offer such resistance. As described by Cooper and Hanlon (2010), continuous growth and survival of L. pneumophila biofilms (1-2 month old at 50 mg/L over an hour) were observed despite high levels of chlorine. An earlier study by Kuchta et al. (1983) also showed different Legionella strains were more resistant to chlorine compared to other coliform bacteria; even more resistant at low chlorine dosages. In terms of its long term efficacy, an environmental surveillance study by García et al. (2008), showed L. pneumophila sero-group 1 survived despite successive episodes of hyperchlorination for 10, 5 and 17 years in a hotel, fishing boat and hospital water system respectively. By far, available studies continue to suggest, hyper chlorination appears to be only effective in its initial stages with bacteria levels often exceeding pre-treatment levels after a short while (Marchesi et al., 2011) (Figure 2). There is also evidence of facilities (e.g. hospitals) switching to other disinfection techniques having previously implemented hyper chlorination (Lin et al., 2011).
Thus, hyper chlorination is inadequate for long term disinfection and only suitable for emergencies or during commissioning (DOH, 2009). Coupled with the above, the after effects of its application e.g. corrosion of pipping material over longer periods and the associated health effects of chlorine by-products such as trihalomethanes linked to cancer is also noteworthy (Gopal et al., 2007; USEPA, 2001; Miller, 2008; DOH, 2009; Mcdonnell et al., 1999). Finally, it has been suggested varying residual concentration due to changes in water flow rates may result in inadequate residual quantity at distal fixture, this, may in the long run have no significant effect on bacteria present (DOH, 2009).
Effect of hyper chlorination on water quality and its application in Africa
Although the use of chlorine eliminates water odour (Wajon et al., 1988), water quality is reduced (organoleptic and chemical) often, as a result of chlorine levels (>0.5 < 1.0 mg/L) (Orsi et al., 2014). In terms of health, an increased risk of bladder cancer also appears to be associated with the consumption of chlorinated water (Cantor, 1997) along with other illnesses such as asthma and dermatitis which have also been reported (Gorchev and Ozolins, 2011; Fawell, 2003). Within Africa, available literature shows hyper chlorination is used extensively. Albeit reports of its effect on human health in countries such as Algeria (Benhamimed and Moulessehoul, 2010), hyper chlorination has been documented as an emergency technique during a Legionnaires outbreak in South Africa (NICD, 2016). Its application in conflict areas or disasters zones e.g. Kenya during Cholera outbreaks, alongside the promotion of hygiene and safe food preparation has also been reported (UNICEF, 2011). More so there is documented evidence on its use in the control of Hepatitis E outbreak in northern Uganda. These, reports show, higher concentration of residual chlorine is often required to facilitate control of the virus (IFRC, 2008). Overall, the use of chlorine within drinking water networks either as centralised or point of use is quite extensive in many African countries e.g. Angola, Cameroon, Ethiopia, Guinea, Kenya, Madagascar, Malawi, Mozambique, Nigeria, Rwanda, Tanzania, Uganda, and Zambia (Peletz and Mahin, 2009; Walfer, 2013).
COPPER-SILVER IONIZATION
Method
Copper-silver ionization involves passing water through a device which applies low potential electricity to electrodes of silver and copper, consequently, dissolving and distributing smaller ions (Cachafeiro et al., 2007). The Copper ions (Cu2+) present, form electrostatic bonds with the negatively charged cell walls of microorganisms (Legionella inclusive) resulting in the disruption of cell wall permeability (Muraca et al., 1990; Lenntech, 2011). On the other hand, the silver ions bond with the DNA and RNA of the microorganism, leading to immobilization and cell death (Lenntech, 2011). Overall, the concentration of ions and the nature of the water system must be carefully evaluated, in order to achieve eradication of Legionella.
Characterization of efficacy, advantages and disadvantages
Despite the conventional argument that most disinfection techniques cannot be used in isolation, there is evidence to suggest, copper-silver ionization continues to gain popularity across the globe as an effective and safe technique so long as ions are monitored according to requisite standards (Cachafeiro et al., 2007). In terms of its effect, its application leads to lysis and cell death by “distortion of cellular permeability coupled with protein denaturation” (USEPA, 2001). Its ability to kill as opposed to suppression or control of bacteria is also well documented (Lin and Vidic, 1996; Lin et al., 1998; DOH 2009). With respect to other microorganism aside Legionella, States et al. (1998) argue, copper silver-ionization is ineffective against amoeba and other non-Legionellaceae bacteria. Nonetheless, there is evidence the technique is efficacious against other waterborne pathogens such as Pseudomonas aeruginosa, Stenotrophomonas maltophilia and Acinetobacter baumannii (Huang et al., 2008). Its application in both hot and cold water point of entry is also reported (Chen et al., 2008).
A survey by Stout and Yu (2003) across 16 US hospitals over a 5 to 11 year period, observed copper-silver ionization was most effective compared to other previously implemented disinfection techniques. They reported 0% positivity for Legionella for 50 and 43% of the hospitals as of 1995 and 2000 respectively. This was against 7 out of 15 of the hospitals reporting 30% Legionella positivity at distal fixtures prior to application. Only a single incidence of Legionnaires was reported after the technique had been implemented. A study by Rohr et al. (1999), also showed copper silver ionization achieved a reduction in Legionella counts from 40,000 to 7 cfu/L during the first year of disinfection (average silver ion concentration <10 ug/L). Nevertheless, an increment of 10,000 cfu/L was observed in the third year over a four-year period (Figure 3). Thus, the study concluded, the effect of the technique was only suitable for short-term applications and influenced by factors such as water temperature and content of silver ions in water (>45°C, up to 66.6°C).
Following the concentration of nontuberculous mycobacteria and legionellae for three and four years respectively on the influence of the technique, Kusnetsov et al. (2001), reported electronically released copper and silver ions were inefficacious at taps and showers of a hospital water system despite an increase in ion concentration in the circulating water. Mòdol et al. (2007) in an evaluation of the impact of the technique after the implementation of other techniques, reported a significant decrease in Legionella counts as well as reduction in nosocomial legionellosis (2.45 to 0.18 cases per 1000 patient discharges)
Overall, although advantages such as ease of installation and maintenance have been reported, difficulty in monitoring residual levels, formation of insoluble hydroxides and the need for periodic cleaning of electrodes are also noteworthy (Lin et al., 2011; Campos et al., 2003). A review by Kim et al. (2002a), on studies conducted by other authors suggests the use of metal ions, “either copper alone or both copper or silver” is a good option for Legionella control especially in hot water recirculation systems. Nonetheless, its long term effect is yet to be listed as a major advantage. There are also studies on its application in swimming pools although peer reviewed literature on its efficacy is rarely been reported (Abad et al., 1994; Beer et al., 1999).
Effect of Copper-Silver Ionization on water quality and its application in Africa
According to Mcdonnell et al. (1999), the oral consumption of ions through the use of copper-silver ionization is often limited as ions are only added to recirculating lines in hot water systems. Largely, copper-silver ionization poses very minimal potential safety hazards compared to other chemical disinfection techniques even though its continuous use is however barely encouraged (Zheng et al., 2012).
In a study on the technique, Lin et al. (2002), found variations in water quality as a cause of its inefficacy as on-site pH measurement were high (8.9). There are also reports on the effect of water type (hard or soft) on the efficacy of the technique (TARN-PURE Ltd, 2016). Within Africa, there seem to very little or non-existent literature on the application of the technique in Legionella control. There are however some studies related to copper and silver metals. In Swaziland, Varkey (2010) reported on the antibacterial effect of copper and silver metals on Coliform and E. Coli through immersion of the metals in water. Paper filters containing AgNP and CuNP were tested on water sourced from contaminated streams in Limpopo South Africa resulting in marked reduction in coliform bacteria and E. coli counts and in the incorporation of a copper mesh in the design of clay pot water filters (CPWFs), E. coli and coliforms concentrations in contaminated water were reported to have reduced markedly (Varkey and Dlamini, 2012; Dankovich and Gray, 2011).
OZONATION
Method
Ozone is an unstable potent biocide and oxidizing agent which must be produced on site due to its short half-life especially as rising temperature can results in increase in decomposition (NRC, 1980). Ozone can be produced in a number of ways notably phosphorus contact, silent discharge, photochemical reactions, and electrochemical reactions (Wei et al., 2016). Generated electrically by exciting oxygento a tri-atomic state
, ozone can be injected to an allowable quantity but should be maintained at a residual dosage.
Characterization of efficacy, advantages and disadvantages
Comparably, ozone is more effective in L. pneumophila control compared to other oxidizing biocides (Dominique et al., 1988). In a review, Kim et al. (2002b) reported there is an appreciable use of ozone across Europe although its better complimented with other disinfectants such as chlorine. In light of it being unstable, ozone does not stay in water sufficiently long to provide the residual effects often required in the control of pathogenic bacteria (Kim et al., 2002b; WHO, 2007; Blanc et al., 2005). Ozone is reported to somewhat more effective at a lower temperature, with a potential of faster destruction of microorganisms at higher pH (Botzenhart and Tarcson, 1993)
In terms of efficacy, Edelstein et al. (1982) documented, ozone reduced L. pneumophilla counts in one wing of an unoccupied hospital with average ozone concentration of 0.79 mg/L.
Blanc et al. (2005) however reported no significant reduction in Legionella counts after the application of just ozonation. Appreciable reduction in Legionella counts were however observed after the complimentary implementation of thermal eradication (Table 1).
Overall, ozone generation consumes a significant amount of energy and thus require a lot of monitoring in order to ensure power is optimized while achieving disinfection targets (Casey et al., 1998). Additionally, its requirement of onsite generation and the use of special equipment as opposed to other disinfection modalities make it less favourable. Based on its quick decomposition characteristics and its lack of residual effect, a growing body of reviews and independent studies show ozonation is best implemented as a secondary disinfection technique (Campos et al., 2003; Kim et al., 2002a; Blanc et al., 2005). Reports of of its instantaneous effect in bacterial inactivation, rapid decomposition and on site generation are however listed as major advantages (Casey et al., 1998; Campos et al., 2003).
Effect of ozonation on water quality and its application in Africa
A varying body of literature shows, ozonation significantly improves water quality either in building water systems or even when used in aqua culture (Davidson et al., 2011; Von Gunten, 2003). A study by Von Gunten, (2003) reported ozone as an excellent disinfectant in the inactivation of protozoa compared to other very conventional disinfectants. In terms of water quality, ozonation has been documented to result in a significant increase in ultraviolet transmittance as well as a reduction in carbonaceous BOD and colour (Davidson et al., 2011). By combining ozonation with UV treatment, available literature has shown the potential for minimizing bromate as well as the oxidation or micro pollutants in water (Meunier et al., 2006). Practically, studies have also shown the application of ozonation for disinfection has a positive impact on distribution water system, reducing both levels of disinfection by products and complaints about the taste and odour of water (Dyksen et al., 2016). Essentially, it is evident problems in water quality that are often addressed with peroxide, chlorine etc. can also be addressed through ozonation (Eagleton, 1999). Within Africa, there is extensive evidence on the application of ozonation although much of its use is not directly aimed at the elimination of L. pneumophillia. The post-ozone plant at Wiggins waterworks which was commissioned in 1984 in South Africa is one such example. The purpose of the plant has been to properly disinfect water by eliminating viruses in raw water pumped from the polluted lower Umgeni river (Rencken, 1994). There is also evidence on the application of ozonation in industrial waste water and drinking water treatment plants in parts of South Africa (Van der Merwe et al., 2012). Its use at the Midvaal water company Durban Water Recycle Plant and Magalies Water plant are also documented (Rajagopaul et al., 2008; Morrison et al., 2012).
UV IRRADIATION
Method
UV disinfection can be applied in two ways: (1) Positioning UV lights at specific points within a given water distribution system that service a designated area or (2) installation of a UV-sterilizers for the disinfection of incoming water. Monochromatic low pressure UV lamps and polychromatic medium pressure lamps are some of the lamps used (Oguma et al., 2004).
Characterization of efficacy, advantages and disadvantages
In terms of efficacy, available literatures shows UV radiation kills bacteria by hampering DNA replication through the production of “thymine dimers” (Gavdy and Gavdy, 1980 as cited in Hambidge, 2001). Typically, there are different types of UV lamb systems although low pressure UV bulb systems are almost an industry standard supplying monochromatic irradiation specific to 254 nm wavelength (Summerfelt, 2003). Its efficacy against other microorganisms is documented elsewhere (Harris et al., 1987; Hijnen et al., 2006; Chevrefils et al., 2006). On the other hand, the use of UV alone in a persistently colonised hospital water distribution system (“point of use application”) showed it was ineffective in the elimination of Legionella (Liu et al., 1995). The concurrent application of other disinfection techniques e.g. Superheat/Flush and shock chlorination however achieved some reduction in Legionella counts. In a study by Franzin et al. (2002) a reduction in Legionella counts (L. pneumophila sero-group 3) was achieved even at distal sites using UV light. The authors therefore concluded UV disinfection could be suitable in small areas of water system. In Hall et al. (2003), UV was efficacious in preventing Legionella contamination over a 13 year period. Overall, despite reports of the extensive application of UV in both cold and hot water systems (Liu et al., 1995; Kim et al., 2002a), its limitations include maintenance against the formation of scales, likelihood of malfunctions, lack of residual protection beyond points of application and turbidity (Muraca et al., 1990; USEPA, 2001; Campos et al., 2003). The use of filters in minimizing the accumulation of scale on UV quatz sleeves has also been reported (Liu et al., 1995). In terms of other advantages, UV light is easy to install (Campos et al., 2003). Conspicuously, continuous monitoring as may be the case in other disinfection modalities is also limited. Finally, although the energy used in typical UV disinfection system in an average size home is comparable to the energy used by a 40 watts bulb (UV Dynamics, 2016), the energy cost associated with technique cannot be ignored.
Effect of UV irradiation on water quality and its application in Africa
Overall, the application of Ultraviolet light (UV-Lamp) is an established and increasingly popular alternative to chemicals for the disinfection of water distribution systems. Interestingly, the quality of water is one of the many defining factors in its application (Wright and Cairns, 1998). Amid it being a cost effective disinfection technology, there is evidence, UV provides no residual effect in water towards the protection against post treatment contamination (Clancy et al., 2000; Said and Otaki, 2013). A study by Choi and Choi (2010) has shown the technology has an effect on dissolved organic matter structure (DOM) in distribution systems including an increase in biodegradability (Frimmel, 1998; Drikas et al., 2004). By far, the aforementioned remains the most documented effect on water quality across an existing body of research (Kruithof et al., 1992; Oppenheimer et al., 1997). Within Africa, a study on a device (UV light 254 nm) that utilizes the technique to disinfect community drinking water demonstrated efficacy for close to 4.5 months; delivering water that meets WHO and USEPA bacteria standards (USEPA, 2001; Gadgil et al., 1998). At the Durban Metro Water and hospice for infants, the application of a UV unit also achieved a reduction in E. coli and total coliforms concentration per local standards (Gadgil et al., 1998). Largely, there is no literature on the application of this technology specifically aimed at Legionella control. There is however extensive publication on its application as a regular water disinfection technology coupled with the proliferation of numerous devices or units that utilize the technology for disinfection (Brahmi and Hassen, 2014; Gadgil et al., 1997). Perhaps, Solar Water Disinfection (SODIS) which is appears to be highly patronised due to the conspicuously low cost implication associated with it compared to the conventional use of UV lamps, positions the use of UV- light as somewhat unpopular. Reports on the efficacy of SODIS and application in developing nations is been reported (Mosler et al., 2013; Murinda and Kraemer 2008; Altherr et al., 2008; Conroy et al., 2001). Nevertheless, its limitations such as the need for sufficient solar radiation, relatively clear water and difficulty in treating large volumes cannot be overlooked (Mintz et al., 2001).
DISCUSSION
This work provides further knowledge on an already explored area of comparing different water disinfection techniques in Legionella control and elimination. Additionally, the study also attempts to identify cases of Legionnaires reportage in Africa as well as the application of some selected disinfection techniques in Legionella control within the continent. The overall aim of the fore going, is to provide an update on some of the most commonly used water disinfection techniques employed in Legionella control so as to provide a pool of evidence based options (locally and internationally) in the event of Legionnaires outbreak within Africa.
Globally, reports on the outbreak of Legionnaires occur almost every year; often reported by the developed countries. Countries such as the United States through the Centre for Diseases Control (CDC) are known to document almost 5,000 cases of Legionnaires’ annually (Dooling et al., 2015). This is no different in Europe. Well-regulated surveillance programmes across almost 35 countries within Europe, exist with the mandate to collect and provide information with regards to the disease (Heuner and Swanson, 2008). The European Surveillance Scheme for Travel Associated Legionnaires Disease now known as EWGLINET, is known to be instrumental in recommending standards for Legionnaires surveillance (Ricketts and Joseph, 2005). The case is however very different in the African context. With the exception of a handful African countries e.g. South Africa, there is very little in terms of institutions or organizations aimed solely at monitoring Legionnaires on the national scale or on the continent at large. The lack of statutory notification of Legionnaires, coupled with clearly defined health based standards is evident in the lack of academic
literature or studies related to Legionnaires on the continent, as may be the case in Europe. For instance, there are very few studies or reports on particular water disinfection techniques aimed at Legionella control or evidence of them being applied during an outbreak as shown in this review. Perhaps, political importance, clinical impact or rareness of disease (Heuner and Swanson, 2008) that are motivating factors in paying attention to most infectious diseases is minimal.
Unfortunately, the argument cannot be made that reportage or studies related to Legionella are very little because proliferation, infection or outbreaks rarely occur. L. pneumophila is known to grow and survive over a wide range of temperature (20, 40 and 50°C) (Rogers et al., 1994; Konishi et al., 2006) and these temperatures are typical in a greater part of sub Saharan Africa. Moreover, there is evidence to suggest temperature increase over land regions across the continent is consistent with anthropogenic climate change (Aalst et al., 2014), thus, the implication of the foregoing are favourable temperature for bacteria proliferation in already precarious water distribution networks across the continent. More so, at the root of the many challenges with water supply are the poor maintenance and servicing culture of already deteriorated pipe networks (Marin, 2009). Many of the water distribution networks are faced with massive leakages, irregular supply and low water pressure; these factors create avenue for easy water contamination (Marin, 2009). Implicitly, much of the water prior to being consumed at distal sites are already contaminated with pathogenic bacteria; a challenge that must be avoided from the onset as a step in achieving Legionella control (Borella et al., 2005; Rangel et al., 1999; WHO, 2007).
On the other hand, evidence of a single most consistent and permanent method at Legionella control is barely been established globally. Our review noted most of the disinfection techniques often had to be combined to achieve long term efficacy; consistent with literature elsewhere. For instance, while techniques such as thermal disinfection record some measure of efficacy, the lack of residual effect days after application, often require the application of other techniques e.g. chlorination. Thus, the application of such methods have demonstrated efficacy only in the short term. Additionally, it would also seem somewhat challenging to flush entire water systems of heavily occupied hotels or hospitals especially as occupancy and monitoring at distal sites are significant in achieving success. In terms of Chlorination, evidence of re-colonization as shown in this review, suggests it can arguably be placed under the category of short term or emergency techniques notwithstanding its residual effect. Moreover, the role of biofilm and Legionella resistance to Chlorine as reported in other literature (Kuchta et al., 1983; Cooper and Hanlon, 2010) imply, larger doses of chlorine are often required to achieve complete elimination. In view of the fact that chlorination is already used extensively as a common water disinfection technique within Africa (Whitacre, 2010), it seems at best, one of the most accessible disinfection techniques to be employed in the event of an outbreak. Chlorine dosage will however have to be based on local regulations or known international standards.
Copper silver ionization appears the most efficacious compared to the other techniques in this review. In addition to its ease of installation, evidence of its application even in hot and cold water systems with keen consideration to ion quantities, provides the basis for arguing, the technique can be employed during outbreaks and over longer periods. Additionally, its ability to kill as opposed to suppression, proves copper-silver ionization will be the most suitable disinfection modality in heavily colonised water distribution networks. The afore highlights, coupled with findings in other literature (Marchesi et al., 2011; Lin et al., 1998) therefore positions copper silver ionization, conceivably as one of the best alternatives for Legionella control.
With Ozonation, albeit, its extensive use within Europe and Africa as shown in this report, the need for onsite generation and special equipment could be challenging in most domestic installation or small public buildings in rural areas; heavily colonised by bacteria. Additionally, its lack of residual effect, energy consumption and need for monitoring, implies the technique will be difficult to apply in colonised water systems in places with less manpower or electricity. Nevertheless, its rapid destruction of microorganism at higher pH (Botzenhart and Tarcson, 1993) along with its ability to compliment other disinfection techniques, positions the technique as a viable option in Legionella control within Africa.
Finally, on the grounds of challenges such as maintenance against the formation of scales, lack of residual effect, use of filters for scale prevention and the need to combine with other disinfection techniques as already evidenced in this report, UV cannot be considered a “singular disinfection method“. Albeit its ease of installation, the lack of evidence of its efficacy in large-scale water systems, suggests UV should be considered in less colonised water systems or systems with little water volume, where greater water quantity can be exposed at point of contact. On the hand, the use of Solar Water Disinfection (SODIS) in Africa as suggested in the earlier part of this study will serve the greater advantage of bacteria control in rural areas especially in the absence of the commonly “advanced technologies” in water disinfection. A foreseeable challenge to this measure will be its inability to be implemented in large scale water systems where treating large volumes of water will pose a challenge (Mintz et al., 2001).
Overall, while all the aforementioned techniques have their respective disadvantages, their proven reliability across different types of buildings and water systems, suggest they can all be described as efficacious in one way or the other. Their implementation will therefore vary on a number of factors such as cost, ease of installation, maintenance, age and design of plumbing system, availability of electricity (for certain techniques), as well as the measure of colonization of the water system under consideration. An overall consideration should however be the prevention of contamination from the onset as reported elsewhere as well as effective monitoring of water system towards the identification of colonization at the early stages. The need for sensitizing the general population about Legionnaires, symptoms as well as factors that can lead to contamination in water distribution networks is also important within Africa.
CONFLICT OF INTERESTS
The authors have not declared any conflict of interests.
REFERENCES
Aalst MV, Adger N, Arent D, Barnett J, Betts R, Bilir E, Yoh G (2014). Climate Change 2014: Impacts, Adaptation, and Vulnerability. Assess. Rep. 5(October 2013):1-76. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Abad FX, Pinto RM, Diez JM, Bosch A (1994). Disinfection of human enteric viruses in water by copper and silver in combination with low levels of chlorine. Appl. Environ. Microbiol. 60(7):2377-2383. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Altherr AM, Mosler HJ, Tobias R, Butera F (2008). Attitudinal and relational factors predicting the use of solar water disinfection: a field study in Nicaragua. Health Edu. Behav. Official Pub. Soc. Public Health Educ. 35(2):207-220. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Beer CW, Guilmartin LE, McLoughlin TF, White TJ (1999). Swimming pool disinfection: efficacy of copper/silver ions with reduced chlorine levels. J. Environ. Health 61(9):9-13. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Benhamimed EA, Moulessehoul S (2010). L'hyperchloration de l'eau de robinet et cancer de la vessie dans la r??gion de Mostaganem (Ouest alg??rien). J. Afr. Du Cancer 2(3):1-6. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Blanc DS, Carrara P, Zanetti G, Francioli P (2005a). Water disinfection with ozone, copper and silver ions, and temperature increase to control Legionella: seven years of experience in a university teaching hospital. J. Hosp. Infect. 60(1):69-72. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Borella P, Guerrieri E, Marchesi I, Bondi M, Messi P (2005). Water ecology of Legionella and protozoan: Environmental and public health perspectives. Biotechnol. Ann. Rev. 11:355-380. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Botzenhart K, Tarcson GOM (1993). Inactivation of Bacteria and Coliphages by Ozone and Chlorine Dioxide in a Continuous Flow Reactor. Water Sci. Technol. 27(3-4). |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Brahmi M, Hassen A (2014). Modeling of ultraviolet (UV) radiation under a large pilot-scale designed for wastewater disinfection and inactivation of selected bacteria of Pseudomonas aeruginosa in a laboratory UV device. Afr. J. Microbiol. Res. 8(16):1735-1748. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Cachafeiro SP, Naveira IM, García IG (2007). Is copper-silver ionisation safe and effective in controlling legionella? J. Hosp. Infect. 67(3):209-216. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Campos C, Loret JF, Cooper AJ, Kelly RF (2003). Disinfection of domestic water systems for Legionella pneumophila. J. Water Supply: Res. Technol. AQUA 52(5):341-354. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Cantor KP (1997). Drinking water and cancer. Cancer Causes Control. 8(3):292-308. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Casey S, Collen M, Lake A (1998). Ozone disinfection. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
CDC (2016). Legionella (Legionnaires' Disease and Pontiac Fever). |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Centre for Respiratory Diseases and, Meningitis, and Division of Public Health, S., and Response, (NICD) (2016). RESPIRATORY DISEASE; Three travel-associated Legionnaires' disease (TALD) cases associated with a hotel in Cape Town. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Chen YS, Lin YE, Liu YC, Huang WK, Shih HY, Wann SR, Chang CL (2008). Efficacy of point-of-entry copper-silver ionisation system in eradicating Legionella pneumophila in a tropical tertiary care hospital: implications for hospitals contaminated with Legionella in both hot and cold water. J. Hosp. Infect. 68(2):152-158. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Chen YS, Liu YC, Lee SSJ, Tsai HC, Wann SR, Kao CH, Lin YSE (2005). Abbreviated duration of superheat-and-flush and disinfection of taps for Legionella disinfection: Lessons learned from failure. Am. J. Infect. Control 33(10):606-610. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Chevrefils G, Caron É, Wright H, Sakamoto G (2006). UV dose required to achieve incremental log inactivation of bacteria, protozoa and viruses. IUVA News 8(1):38-45. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Choi Y, Choi YJ (2010). The effects of UV disinfection on drinking water quality in distribution systems. Water Res. 44(1):115-122. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Clancy JL, Bukhari Z, Hargy TM, Bolton JR, Dussert BW, Marshall MM (2000). Using UV to inactivate Cryptosporidium. J. Am. Water Works Assoc. 92(9):97-104. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Cold Spring Harbor Laboratory (2008). Worldwide-distributed Clone Of Bacteria Responsible For Legionnaire's Disease Identified. Retrieved August 15, 2016. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Conroy RM, Meegan ME, Joyce T, McGuigan K, Barnes J (2001). Solar disinfection of drinking water protects against cholera in children under 6 years of age. Arch. Dis. Childhood 85(4):293-295. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Cooper IR, Hanlon GW (2010). Resistance of Legionella pneumophila serotype 1 biofilms to chlorine-based disinfection. J. Hosp. Infect. 74(2):152-159. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Dankovich TA, Gray DG (2011). Bactericidal paper impregnated with silver nanoparticles for point-of-use water treatment. Environ. Sci. Technol. 45(5):1992-1998. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Davidson J, Good C, Welsh C, Summerfelt S (2011). The effects of ozone and water exchange rates on water quality and rainbow trout Oncorhynchus mykiss performance in replicated water recirculating systems. Aquacult. Eng. 44(3):80-96. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Department of Health (DOH) (2009). Independent review of evidence regarding selection of techniques for the suppression of legionella in water supplies of hospitals and other health care premises. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Dominique EL, Tydall RL, Mayberry WR, Pancorbo OC (1988). Effects of three oxidizing biocides on Legionella pneumophila serogroup 1. Appl. Environ. Microbiol. 54(3):741-747. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Dooling KL, Toews KA, Hicks LA, Garrison LE, Bachaus B, Zansky S, Carpenter LR, Schaffner B, Parker E, Petit S, Thomas A, Thomas S, Mansmann R, Morin C, White B, Langley GE (2015). Active Bacterial Core Surveillance for Legionellosis - United States, 2011-2013. MMWR Morb Mortal Wkly Rep. 64(42):1190-1193. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Drikas M, Thomson J, Roddick FA (2004). Vacuum ultraviolet irradiation for natural organic matter removal. J. Water Supply Res. Technol. - AQUA 53(4):193-206. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Dyksen JE, Spencer C, Khiari D (2016). Study Examines How Disinfection Changes Affect Water Quality. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Eagleton J (1999). Ozone in Drinking Water Treatment. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Edelstein PH, Whittaker RE, Kreiling RL, Howell CL (1982). Efficacy of ozone in eradication of Legionella pneumophila from hospital plumbing fixtures. Appl. Environ. Microbiol. 44(6):1330-1334. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Fawell J (2003). Drinking Water Contaminants. British Med. Bull. 68:199-208. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Franzin L, Cabodi D, Fantino C (2002). Evaluation of the efficacy of ultraviolet irradiation for disinfection of hospital water contaminated by Legionella. J. Hosp. Infect. 51(4):269. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Frimmel FH (1998). Impact of light on the properties of aquatic natural organic matter. Environ. Int. 24:559-571. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Gadgil A, Drescher A, Greene D, Miller P, Motau C, Stevens F (1997). Field-testing UV disinfection of drinking water. In WEDC conference: water and sanitation for all, Durban (South Africa). |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Gadgil A, Greene D, Drescher A, Miller P, Kibata N (1998). Low Cost UV Disinfection System For Developing Countries: Field Tests In South Africa. In First International Symposium on Safe Drinking Water in Small Systems. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
García M, Baladrón B, Gil V, Tarancon M, Vilasau A, Iba-ez A, Pelaz C (2008). Persistence of chlorine-sensitive Legionella pneumophila in hyperchlorinated installations. J. Appl. Microbiol. 105(3):837-847. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Gilman RH, Skillicorn P (1985). Boiling of drinking-water: Can a fuel-scarce community afford it? Bull. World Health Organ. 63(1):157-163. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Gopal K, Tripathy SS, Bersillon JL, Dubey SP (2007). Chlorination byproducts, their toxicodynamics and removal from drinking water. J. Hazard. Mater. 140(1-2):1-6. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Gorchev HG, Ozolins G (2011). WHO guidelines for drinking-water quality. WHO Chronicle 38(3):104-108. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Groothuis DG, Veenendaal HR, Dijkstra HL (1985). Influence of temperature on the number of Legionella pneumophila in hot water systems. J. Appl. Bacteriol. 59(6):529-536. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Hall KK, Giannetta ET, Getchell-White SI, Durbin LJ, Farr BM (2003). Ultraviolet light disinfection of hospital water for preventing nosocomial Legionella infection: a 13-year follow-up. Infect. Control Hosp. Epidemiol. 24(8):580-583. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Hambidge A (2001). Reviewing efficacy of alternative water treatment techniques. Health Estate. 55(6):23-25. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Harris GD, Adams VD, Sorensen DL, Curtis MS (1987). Ultraviolet inactivation of selected bacteria and viruses with photoreactivation of the bacteria. Water Res. 21(6):687-692. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Heuner K, Swanson M (2008). Legionella: Molecular Microbiology. (K. Heuner & M. Swanson, Eds.). Caister Academic Press. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Hijnen WAM, Beerendonk EF, Medema GJ (2006). Inactivation credit of UV radiation for viruses, bacteria and protozoan (oo)cysts in water: A review. Water Res. 40(1):3-22. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Hilbi H, Jarraud S, Hartland E, Buchrieser C (2010). Update on Legionnaires' disease: Pathogenesis, epidemiology, detection and control: MicroMeeting. Mol. Microbiol. 76:1-11. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Huang HI, Shih HY, Lee CM, Yang TC, Lay JJ, Lin YE (2008). In vitro efficacy of copper and silver ions in eradicating Pseudomonas aeruginosa, Stenotrophomonas maltophilia and Acinetobacter baumannii: Implications for on-site disinfection for hospital infection control. Water Res. 42(1-2):73-80. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
International Federation of Red Cross And Red Crescent Societies (IFRC). (2008). Emergency appeal ; Uganda: Epidemics. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Kim BR, Anderson JE, Mueller SA, Gaines WA, Kendall AM (2002a). Disinfection of domestic water systems for Legionella pneumophila. Water Res. 36(18):4433-4444 |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Kim BR, Anderson JE, Mueller SA, Gaines WA, Kendall AM (2002b). Literature review - Efficacy of various disinfectants against Legionella in water systems. Water Res. 36(18):4433-4444. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Konishi T, Yamashiro T, Koide M, Nishizono A (2006). Influence of temperature on growth of Legionella pneumophila biofilm determined by precise temperature gradient incubator. J. Biosci. Bioeng. 101(6):478-484. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Kruithof JC, Van der Leer RC, Hijnen WAM (1992). Practical experiences with UV disinfection in the Netherlands. J. Water SRT - Aqua 41(2):88-94. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Kuchta JM, States SJ, McNamara AM, Wadowsky RM, Yee RB (1983). Susceptibility of Legionella pneumophila to chlorine in tap water. Appl. Environ. Microbiol. 46(5):1134-1139. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Kümpers P, Tiede A, Kirschner P, Girke J, Ganser A, Peest D (2008). Legionnaires' disease in immunocompromised patients: A case report of Legionella longbeachae pneumonia and review of the literature. J. Med. Microbiol. 57(3). |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Kusnetsov J, Iivanainen E, Elomaa N, Zacheus O, Martikainen PJ (2001). Copper and silver ions more effective against Legionellae than against mycobacteria in a hospital warm water system. Water Res. 35(17):4217-4225. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Lenntech (2011). Disinfectants Copper-silver ionization. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Lin EY, Stout JE, Yu VL (2011). Controlling Legionella in hospital drinking water: an evidence-based review of disinfection methods. Infect. Control Hosp. Epidemiol. 32(2):166-173. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Lin SY, Stout JE, Yu VL, Vidic RD (1998). Disinfection of water distribution systems for Legionella. Semin. Respir. Infect. 13(2):147-59. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Lin Y, Vidic R (1996). Individual and combined effects of copper and silver ions on inactivation of Legionella pneumophila. Water Res. 30(8):1905-1913. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Lin YSE, Vidic RD, Stout JE, Yu VL (2002). Negative effect of high pH on biocidal efficacy of copper and silver ions in controlling Legionella pneumophila. Appl. Environ. Microbiol. 68(6):2711-2715. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Liu Z, Stout JE, Tedesco L, Boldin M, Hwang C, Yu VL (1995). Efficacy of ultraviolet light in preventing Legionella colonization of a hospital water distribution system. Water Res. 29(10):2275-2280. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Luby SE, Syed AH, Atiullah N, Faizan MK, Fisher-Hoch S (2000). Limited effectiveness of home drinking water purification efforts in Karachi, Pakistan. Int. J. Infect. Dis. 4(1):3-7. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Marchesi I, Marchegiano P, Bargellini A, Cencetti S, Frezza G, Miselli M, Borella P (2011). Effectiveness of different methods to control legionella in the water supply: ten-year experience in an Italian university hospital. J. Hosp. Infect. 77(1):47-51. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Marin P (2009). Public Private Partnerships for Urban Water Utilities: A Review of developing countries. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Mcdonnell G, Russell AD, Block SS (1999). Disinfection, sterilization, and preservation. Clin. Microbiol. Rev. 12:147-179 |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Meunier L, Canonica S, von Gunten U (2006). Implications of sequential use of UV and ozone for drinking water quality. Water Res. 40(9):1864-1876. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Miller R (2008). Preventing Legionella: Common Disinfection Techniques. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Mintz ED, Bartram J, Lochery P, Wegelin M (2001). Not just a drop in the bucket: Expanding access to point-of-use water treatment systems. Am. J. Public Health 91(10):1565-1570. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Mòdol J, Sabrià M, Reynaga E, Pedro-Botet ML, Sopena N, Tudela P, Rey-Joly C (2007). Hospital-acquired legionnaires disease in a university hospital: impact of the copper-silver ionization system. Clin. Infect. Dis. Official Pub. Infect. Dis. Soc. Am. 44:263-265. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Morrison S, Venter A, Barnard S (2012). A case study to determine the efficacy of ozonation in purification processes. Water SA 38(1). |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Mosler HJ, Kraemer SM, Johnston RB (2013). Achieving long-term use of solar water disinfection in Zimbabwe. Public Health 127(1):92-98. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Mouchtouri V, Velonakis E, Hadjichristodoulou C (2007). Thermal disinfection of hotels, hospitals, and athletic venues hot water distribution systems contaminated by Legionella species. Am. J. Infect. Control 35(9):623-627. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Muraca P, Stout JE, Yu VL (1987). Comparative assessment of chlorine, heat, ozone, and UV light for killing Legionella pneumophila within a model plumbing system. Appl. Environ. Microbiol. 53(2):447-453. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Muraca PW, Yu VL, Goetz A (1990). Disinfection of water distribution systems for legionella: a review of application procedures and methodologies. Infect. Control Hosp. Epidemiol. 11(2):79-88. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Murinda S, Kraemer S (2008). The potential of solar water disinfection as a household water treatment method in peri-urban Zimbabwe. Phys. Chem. Earth Parts A/B/C 33(8-13):829-832. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
National Research Council (US) Safe Drinking Water Committee. (NRC) (1980). The Disinfection of Drinking Water. National Academies Press (US), 2. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Oguma K, Katayama H, Ohgaki S (2004). Photoreactivation of Legionella pneumophila after inactivation by low- or medium-pressure ultraviolet lamp. Water Res. 38(11):2757-2763. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|